Total Protection for Life

(303) 790-7656

Surge Protection Products

 

  ST Series

 
System Features


Providing the highest level of protection with the lowest let-through voltage in the industry

Fail-Safe Design

Optional Component Level Dual Fusing

NEMA LS1 Compliance -
single pulse tested at independent 3rd party lab (NEMA LS 1, 2.2-9 and 3-9)

 


Two suppression technologies: MOV and Enhanced Transient Filter


UL 1283 Tracking Filter

Ultra, Compact Footprint - efficiency and performance

30 Year Unlimited Free Replacement Warranty

Form C dry relay contacts and audible alarm with silence button

Specifications

GENERAL SPECIFICATIONS


Maximum Rated Surge Current:
            ST080 : 80kA per phase; 40kA per mode
            ST120 : 120kA per phase; 60kA per mode
            ST160 : 160kA per phase; 80kA per mode
            ST240 : 240kA per phase; 120kA per mode
            ST300 : 300kA per phase; 150kA per mode
            ST400 : 400kA per phase; 200kA per mode
Application: See product specific datasheet
Design: Optimum performing parallel hybrid with dual
component level fusing
Warranty: 30-Year Unlimited Free Replacement Warranty
Safety Listing: UL 1449 2nd Edition, cUL, UL 1283 Filter

ELECTRICAL SPECIFICATIONS

Mode of Protection: All Mode. L-N, L-L, L-G, & N-G
Input Power Frequency: 40-440Hz (47-64 Hz with enhanced filter option)
Response Time: < 1 nanosecond
Standard Monitoring: Status indicator lights (one per phase
& one service LED); Form C dry relay contacts for suppressor status; Audible alarm with silence button
Short Circuit Current Rating: 200 kAIC with CLF version
No upstream over-current protection required. (non-CLF
version: 200kAIC using 60A Class J fuse)

MECHANICAL SPECIFICATIONS

Dimensions (approx.):
ST080, ST120 & ST160 : 8"H x 6"W x 6"D
ST240, ST300 & ST400 : 10"H x 8"W x 6"D
Enclosure: Steel. Weather-proof. NEMA 4.
Connection:
ST080, ST120 & ST160 :
Pre-wired with 36" of #10 AWG conductor
ST240, ST300 & ST400 :
Hardwired via internal lugs #10 AWG - #3 AWG
Mounting: Multi-point mounting feet
Operating Environment: -40° C to 70° C (-40° F to 160° F),
5% to 95% non-condensing humidity
Weight: 12 lbs. (5.4 kg)
ST080, ST120 & ST160 : 12 lbs. (5.4 kg)
ST240, ST300 & ST400 : 24 lbs. (10.9 kg)


AVAILABLE CONFIGURATIONS
 
Model Number Description
TK-STxxx-1P120 120VAC, 1φ 2-wire + grd
TK-STxxx-1P240 240VAC, 1φ 2-wire + grd
TK-STxxx-1S240 120/240VAC, 1φ SPLIT-PHASE, 3-wire + grd
TK-STxxx-3Y208 120/208VAC, 3φ WYE, 4-wire + grd
TK-STxxx-3Y480 277/480VAC, 3φ WYE, 4-wire + grd
TK-STxxx-3Y600 347/600VAC, 3φ WYE, 4-wire + grd
TK-STxxx-3D240 120/240VAC, 3φ high-leg DELTA, 4-wire + grd (B phase must be 208V)
TK-STxxx-240NN 240VAC, 3φ DELTA, 3-wire + grd
TK-STxxx-380NN 380VAC, 3φ DELTA, 3-wire + grd
TK-STxxx-480NN 480VAC, 3φ DELTA, 3-wire + grd
TK-STxxx-600NN 600VAC, 3φ DELTA, 3-wire + grd

xxx denotes surge rating per phase (080, 120, 160, 240, 300 and 400)

AVAILABLE OPTION
Order as a Suffix Example: TK- ST080-3Y208-FL

• Enhanced Transient Filter (ETF): add suffix "-F"
• Component Level Fusing (CLF): add suffix "-L"
• Surge Counter: add suffix "-B"
• NEMA 4X Stainless Steel Enclosure: add suffix "-XX"

Order as a Separate Item (30 Year Warranty)
Fused Disconnect Switch Non-Fused Disconnect Switch:
     ST080, 120, & 160:
        DF-200kAIC-60A-3/4
        DF-200kAIC-60A-1
     ST240, ST300 & ST400:
        DN-200kAIC-60A-3/4
        DN-200kAIC-60A-1

EMI / RFI FILTER ATTENUATION - M IL STANDARD 220B

Frequency Attenuation
1kHz 2 dB
10kHz 17 dB
100kHz 40 dB
1MHz 18 dB
10MHz 6 dB
100MHz 1 dB
Max. Attenuation Frequency 41 dB @ 106 kHz

 

 